MODEL |
H1-3.0-E |
H1-3.7-E |
H1-4.6-E |
H1-5.0-E |
H1-6.0-E |
AC1-3.0-E |
AC1-3.7-E |
AC1-4.6-E |
AC1-5.0-E |
AC1-6.0-E |
PV INPUT (FOR HYBRID ONLY) |
Maximum Input Power [W] |
3900 |
4680 |
5980 |
6500 |
7800 |
Maximum Input Voltage [V] |
600 |
Input Start Voltage [V] |
75 |
Rated Input Voltage [V] |
360 |
MPPT Operating Voltage Range [V] |
80 ~ 550 |
Maximum Input Current [A] |
13,5/13,5 |
Maximum Short Circuit Current [A] |
15/15 |
Number of Independent MPP Trackers |
2 |
Number of Strings per MPP Tracker |
1 |
BATTERY CONNECTION |
Battery Type |
Batería de LiTIo (LFP) |
Battery Voltage [V] |
85 ~ 450 |
Maximum Charge / Discharge current [A] |
40 |
Communication interface |
CAN (Inverter Communication), RS485 (BMS Update) |
AC Input and Output (GRID) |
Maximum AC Input Power [VA] |
7000 |
7680 |
9600 |
10000 |
12000 |
Maximum AC Input Current (per phase) [A] |
31,8 |
34,9 |
43,6 |
45,5 |
54,5 |
Rated Output Power [W] |
3000 |
3680 |
4600 |
5000 |
6000 |
Maximum Apparent Output Power [VA] |
3300 |
4048 |
5060 |
5500 |
6600 |
Rated Output Current (per phase) [A] |
13,0 |
16,0 |
20,0 |
21,7 |
26,1 |
Maximum Output Current [A] |
14,3 |
17,6 |
22,0 |
23,9 |
28,7 |
Nominal Grid Voltage [V] |
220/230/240 |
Nominal Grid Frequency [Hz] |
50/60 |
Power Factor |
1 (Adjustable from 0.8 leading to 0.8 lagging) |
THDi [%] |
<3 @ rated power |
EPS OUTPUT (WITH BATTERY) |
Maximum Apparent Output Power [VA] |
5000 |
5000 |
6000 |
6000 |
6000 |
Maximum Apparent Output Power (60 s) (VA) |
6000 |
6000 |
7200 |
7200 |
7200 |
Maximum Current(per phase)[A] |
21,7 |
21,7 |
26,1 |
26,1 |
26,1 |
Rated Output Voltage [V] |
220/230/240 |
Rated output frequency [Hz] |
50/60 |
Power Factor |
1 (Adjustable from 0.8 leading to 0.8 lagging) |
THDv (Linear load) [%] |
< 2 @ rated power |
Switching time [ms] |
<20 |
EFFICIENCY |
European efficiency [%] |
97,00 |
Maximum Efficiency [%] |
97,80 |
Maximum Battery Charging Efficiency |
98,50 |
(PV to BAT) (Full Charge) [%] |
Maximum Battery Discharge Efficiency |
97,00 |
(BAT to AC) (full charge) [%] |
PROTECTION |
Insulation Monitoring |
Sí |
Residual Current Monitoring |
Sí |
DC Reverse Polarity Protection |
Sí |
Protection against the isolated island effect |
Sí |
short circuit protection |
Sí |
AC Overcurrent / Overvoltage Protection |
Sí |
Interruptor de DC |
Sí |
SPD |
DC: Type II, / AC: Type III |
GENERAL DATA |
Dimensions (WxHxD) [mm] |
430*410*178 |
Weight [kg] |
23 |
Facility |
wall |
topology |
without transformer |
cooling method |
NaturaL |
Sound Emission [dB] |
35 |
Maximum Operating Altitude [m] |
2000 |
Operating Temperature Range [°C] |
-25 ~ 60 |
Humidity (No Condensation) [%] |
0 ~ 100 |
Protection Level |
IP65 |
Consumption in Standby Mode [W] |
<10 |
Monitoring Module |
WiFi, LAN, 4G, GPRS ( Optional ) |
Communication |
2 * RS485, DRM, Ripple Control, USB |
Screen |
LCD, Applications, Websites |
STANDARD COMPLIANCE (MORE AVAILABLE UPON REQUEST) |
Security |
EN 62109-1, EN 62109-2 |
|
EMC |
EN 61000-6-2, EN 61000-6-3 |
Grid Regulation |
EN50549-1, C10 / 11, VDE-AR-N 4105, G98, G99, CEI 0-21, NRS 097-2-1, AS / NZS 4777.2 |