60KTLX-G3 |
80KTLX-G3 |
Input (DC) |
Recommended max. input power (Wp) |
90000 |
120000 |
Number of MPP tracker |
6 |
Number of DC inputs |
2 per MPPT |
Max. input voltage (V) |
1100 |
Start-up voltage (V) |
200 |
Rated input voltage (V) |
620 |
MPPT operating voltage range (V) |
180 – 1000 |
Full power MPPT voltage range (V) |
550 – 800 |
Max. input MPPT current (A) |
6*32 |
6*40 |
Max. input short circuit current (A) |
6*50 |
6*60 |
Output (AC) |
Rated power (W) |
60000 |
80000 |
Max. AC power (VA) |
66000 |
88000 |
Max. output current (A) |
100 |
133.3 |
Rated grid voltage |
3 / N / PE, 230 / 400 |
Grid voltage range |
310 – 480 Vac (according to local standard) |
Rated frequency |
50 / 60 Hz |
Grid frequency range |
45 – 55 Hz / 55 – 65 Hz (according to local standard) |
Active power adjustable range |
0 – 100% |
THDi |
< 3% |
Power factor |
1 default (adjustable +/-0.8) |
Performance |
Max. efficiency |
98.70% |
European weighted efficiency |
98.20% |
Protections |
DC reverse polarity protection |
Yes |
Anti-islanding protection |
Yes |
Leakage current protection |
Yes |
Ground fault monitoring |
Yes |
PV-array string fault monitoring |
Yes |
Anti reverse power function |
Yes |
DC switch |
Optional |
Input / output SPD |
PV: type II standard, optional: type I. AC: type II standard |
Communication |
Communication |
RS485 / WiFi / Bluetooth, optional: Ethernet |
General data |
Ambient temperature range |
30℃ – 60℃ |
Self-comsumption at night (W |
< 2 |
Topology |
Transformerless |
Degree of protection |
IP66 |
Allowable relative humidity range |
0 – 100% |
Max. operating altitude |
4000 m |
Weight (kg) |
50 |
Cooling |
Fan |
Dimension (mm) |
687*561*275 |
Display |
LCD, App via Bluetooth |
Warranty |
10 years, optional: up to 20 years |
Standard |
EMC |
EN 61000-6-2, EN 61000-6-3, EN 61000-3-11, EN 61000-3-12 |
Safety standards |
IEC 62109-1/2, IEC 62116, IEC 61727, IEC 61683, IEC 60068 (1,2,14,30), IEC 60255 |
Grid standards |
VDE V 0124-100, V 0126-1-1, VDE-AR-N 4105, CEI 0-21 / CEI 0-16, UNE 206 007-1, EN 50549, G99, EN 50530 |